Description
Sized for selective feeders, this breaker combines a compact XT2S 160 body with full Ekip LSIG protection for long-time, short-time, instantaneous, and ground-fault settings. Front landings keep routing tidy and speed commissioning, and for packaged boards with drawings and FAT, align your project with our industrial panel fabrication to streamline delivery.
Key Specifications – Power Distribution XT2S 160
- 
Model: XT2S 160 Ekip LSIG In=63 A 
- 
Rated current (In): 63 A 
- 
Poles: 3P 
- 
Mounting: Fixed (F) 
- 
Terminals: Front – Front (F F) 
- 
Trip unit: Ekip LSIG – electronic 
- 
Icu: 50 kA at 240 V AC, 70 kA at 380 V AC 
Highlights
- 
Full LSIG functionality enables tight coordination and fast clearing 
- 
Compact frame fits dense LV boards and MCCs 
- 
Front-terminal layout reduces bend radii and install time 
- 
Stable platform for industrial and commercial feeders 
Typical Uses
- 
LV switchboard mains and selective feeders 
- 
MCC incomers with ground-fault requirements 
- 
Commercial risers and process distribution 
- 
Retrofit upgrades where front landing is preferred 
Installation & Support
Mount on plate or rail, torque conductors to spec, then program LSIG thresholds per coordination study. Commission with insulation, functional, and trip tests.
- 